What Lux Level Do You Actually Need?

  • What Lux Level Do You Actually Need?

    What lux level do you need for an office, classroom, shop or warehouse? A plain-English guide to BS EN 12464-1 levels and emergency lighting.

    5 minute read

What is a lux, in plain English?

A lux is simply a measure of how much light lands on a surface — your desk, a classroom table, a warehouse floor. One lux is one lumen spread over one square metre. You do not need the most light possible. You need the right amount for the job being done in that space. Too little and people strain to see, make mistakes and work less safely. Too much and you get glare, headaches and a bigger electricity bill for no benefit. The figures below are maintained illuminance — the level the lighting should still deliver over time, not just on the day it is installed. They come from BS EN 12464-1, the main standard for lighting indoor workplaces, used alongside CIBSE guidance, including the SLL Code for Lighting and LG5 for education.

Recommended lux levels at a glance

Space Lux Glare limit (UGR) Uniformity
General office / open plan 500 lux 19 0.6
Meeting rooms 500 lux 19 0.6
Reception 300 lux 22 0.6
Filing and copying 300 lux 19 0.6
Corridors and stairs 100 lux 28 0.4
Classrooms (general teaching) 300 lux 19 0.6
Whiteboard / teaching wall 500 lux vertical 19 0.7
Science labs and practical rooms 500 lux 19 0.6
Retail sales floor 300 lux 22 0.6
Tills and wrapping 500 lux 19 0.6
Warehouse packing and inspection 300 lux 22 0.6
Warehouse racking aisles (manned) 150 lux 22 0.4
Industrial fine assembly 500 lux 22 0.6
Industrial precision work 750 lux 19 0.7

Source: BS EN 12464-1 recommended levels, as published on IJF Lighting’s Lighting Levels, Emergency Lighting & Standards page. Use these as a guide — every project still needs site-specific lighting calculations.

Notice the pattern: detailed work needs more light. Reading, writing and screen work in an office sit at 500 lux. Moving safely through a corridor needs only 100 lux. Very fine, precise industrial work needs the most, at 750 lux.

Brighter is not always better: glare and uniformity

Two numbers matter alongside lux. UGR is a glare rating — lower is more comfortable. Offices should be at UGR 19 or lower, so screens stay readable and eyes do not tire. Uniformity is how evenly the light is spread. A room with one bright pool and dark corners can average the right lux and still feel wrong. That is why simply adding more fittings rarely fixes a poor room. Position, glare control and even spread matter as much as the headline lux figure.

Emergency lighting, without the jargon

Emergency lighting is the lighting that comes on when the normal power fails, so people can leave safely. The current standards are BS 5266-1:2025, BS EN 1838:2024 and BS EN 50172:2024. In plain terms:

  • Escape routes: at least 1 lux at floor level across the full width of the route — under the 2024 standard this is no longer measured on the centre line only.
  • Open areas (to prevent panic): at least 0.5 lux at floor level, excluding a 0.5 m border around the edge.
  • High-risk task areas: at least 15 lux, or 10% of the normal task lighting, whichever is greater.
  • Fire-fighting equipment, call points and first-aid points: 5 lux, measured vertically at the point.
  • Speed: 50% of the required light within 5 seconds, and 100% within 60 seconds.
  • Along an escape route, the brightest-to-dimmest ratio should be no worse than 40:1.
  • Duration and testing: 1 hour minimum, with 3 hours common where a building is not evacuated straight away. Test monthly with a short test, and once a year with a full-duration test.

Energy, BREEAM and your neighbours

Getting the level right also saves energy. Lighting that is designed to the task — rather than flooding a whole room — supports BREEAM Hea 01 Visual Comfort (glare control, daylight, view out and occupant control) and Ene 01 Energy Performance, where IJF designs use high-efficacy LED fittings, presence detection and daylight dimming, targeting 8 W/m2 or less for office general lighting. Outside, good design should not spill light into neighbours’ windows. IJF designs to the Institution of Lighting Professionals guidance on obtrusive light and BS EN 12464-2, limiting sky glow, light trespass and glare, and using shielded fittings and curfew dimming where needed. That also supports BREEAM Pol 04.

Three mistakes we see most often

  • Guessing the level — choosing fittings by eye, then finding the room is too dim for inspection or too bright for screens.
  • Chasing lux and ignoring glare — hitting 500 lux with a UGR well above 19, so the room passes on paper and hurts in practice.
  • Skipping the calculation — no site-specific calculation means no evidence for building control, BREEAM or a client who asks how the level was chosen.

So, what should you do next?

Start with the table above to get a feel for the level your space needs. Then get it checked properly. A lighting calculation takes your actual room — its size, ceiling height, surfaces, daylight and tasks — and proves the design will deliver the right lux, glare and uniformity before anything is bought or installed.