A lux is simply a measure of how much light lands on a surface — your desk, a classroom table, a warehouse floor. One lux is one lumen spread over one square metre. You do not need the most light possible. You need the right amount for the job being done in that space. Too little and people strain to see, make mistakes and work less safely. Too much and you get glare, headaches and a bigger electricity bill for no benefit. The figures below are maintained illuminance — the level the lighting should still deliver over time, not just on the day it is installed. They come from BS EN 12464-1, the main standard for lighting indoor workplaces, used alongside CIBSE guidance, including the SLL Code for Lighting and LG5 for education.
| Space | Lux | Glare limit (UGR) | Uniformity |
|---|---|---|---|
| General office / open plan | 500 lux | 19 | 0.6 |
| Meeting rooms | 500 lux | 19 | 0.6 |
| Reception | 300 lux | 22 | 0.6 |
| Filing and copying | 300 lux | 19 | 0.6 |
| Corridors and stairs | 100 lux | 28 | 0.4 |
| Classrooms (general teaching) | 300 lux | 19 | 0.6 |
| Whiteboard / teaching wall | 500 lux vertical | 19 | 0.7 |
| Science labs and practical rooms | 500 lux | 19 | 0.6 |
| Retail sales floor | 300 lux | 22 | 0.6 |
| Tills and wrapping | 500 lux | 19 | 0.6 |
| Warehouse packing and inspection | 300 lux | 22 | 0.6 |
| Warehouse racking aisles (manned) | 150 lux | 22 | 0.4 |
| Industrial fine assembly | 500 lux | 22 | 0.6 |
| Industrial precision work | 750 lux | 19 | 0.7 |
Source: BS EN 12464-1 recommended levels, as published on IJF Lighting’s Lighting Levels, Emergency Lighting & Standards page. Use these as a guide — every project still needs site-specific lighting calculations.
Notice the pattern: detailed work needs more light. Reading, writing and screen work in an office sit at 500 lux. Moving safely through a corridor needs only 100 lux. Very fine, precise industrial work needs the most, at 750 lux.
Two numbers matter alongside lux. UGR is a glare rating — lower is more comfortable. Offices should be at UGR 19 or lower, so screens stay readable and eyes do not tire. Uniformity is how evenly the light is spread. A room with one bright pool and dark corners can average the right lux and still feel wrong. That is why simply adding more fittings rarely fixes a poor room. Position, glare control and even spread matter as much as the headline lux figure.
Emergency lighting is the lighting that comes on when the normal power fails, so people can leave safely. The current standards are BS 5266-1:2025, BS EN 1838:2024 and BS EN 50172:2024. In plain terms:
Getting the level right also saves energy. Lighting that is designed to the task — rather than flooding a whole room — supports BREEAM Hea 01 Visual Comfort (glare control, daylight, view out and occupant control) and Ene 01 Energy Performance, where IJF designs use high-efficacy LED fittings, presence detection and daylight dimming, targeting 8 W/m2 or less for office general lighting. Outside, good design should not spill light into neighbours’ windows. IJF designs to the Institution of Lighting Professionals guidance on obtrusive light and BS EN 12464-2, limiting sky glow, light trespass and glare, and using shielded fittings and curfew dimming where needed. That also supports BREEAM Pol 04.
Start with the table above to get a feel for the level your space needs. Then get it checked properly. A lighting calculation takes your actual room — its size, ceiling height, surfaces, daylight and tasks — and proves the design will deliver the right lux, glare and uniformity before anything is bought or installed.
IJF Lighting provides lighting calculations, measured photometric data and a design that meets the standards in this post — for commercial, residential, architectural and industrial projects across the UK, from Milton Keynes. Contact IJF Lighting for a free, no-obligation quote.