In summary: This page is for building owners, facilities managers, architects and designers who need to know what lighting levels and emergency lighting their project must meet. It summarises the key UK and European standards IJF Lighting designs to, including recommended lux levels, emergency lighting requirements, BREEAM lighting credits and how to avoid obtrusive light. Use it as a guide — every project still needs site-specific lighting calculations.
IJF Lighting designs commercial, residential, architectural and industrial lighting to the relevant UK and European standards. This page summarises the levels and standards we work to. Values are maintained illuminance (Em) and are a guide — every project needs site-specific lighting calculations.
| Space | Lux | UGR | Uniformity |
|---|---|---|---|
| General office / open plan | 500 lux | 19 | 0.6 |
| Meeting rooms | 500 lux | 19 | 0.6 |
| Reception | 300 lux | 22 | 0.6 |
| Filing and copying | 300 lux | 19 | 0.6 |
| Corridors and stairs | 100 lux | 28 | 0.4 |
| Classrooms (general teaching) | 300 lux | 19 | 0.6 |
| Whiteboard / teaching wall | 500 lux vertical | 19 | 0.7 |
| Science labs and practical rooms | 500 lux | 19 | 0.6 |
| Retail sales floor | 300 lux | 22 | 0.6 |
| Tills and wrapping | 500 lux | 19 | 0.6 |
| Warehouse packing and inspection | 300 lux | 22 | 0.6 |
| Warehouse racking aisles (manned) | 150 lux | 22 | 0.4 |
| Industrial fine assembly | 500 lux | 22 | 0.6 |
| Industrial precision work | 750 lux | 19 | 0.7 |
BS EN 12464-1 is the principal standard for lighting of indoor workplaces. CIBSE guidance, including the SLL Code for Lighting and LG5 for education, is used alongside it.
Hea 01 Visual Comfort (up to 6 credits): glare control to BS EN 12464-1 UGR limits (UGR 19 or lower in offices), daylight provision (typically a daylight factor of 2% or more in occupied spaces), view out, and occupant control of lighting by zone.
Ene 01 Energy Performance: high-efficacy LED luminaires (130 lm/W or better), presence/absence detection, daylight dimming and task-ambient design to reduce installed load — target 8 W/m² or less for office general lighting. Lighting calculations (lux, uniformity and UGR) are required as BREEAM evidence.
Ene 03 External Lighting and Pol 04 Reduction of Night-Time Light Pollution: energy-efficient external fittings and controls to limit spill and upward light.
Good design should not spill light onto neighbouring properties. We design to the Institution of Lighting Professionals (ILP) Guidance Notes for the Reduction of Obtrusive Light and BS EN 12464-2, limiting sky glow, light trespass into windows, glare to neighbours and upward light, and using curfew dimming and shielded fittings where needed. This also supports BREEAM Pol 04.
Related schemes: where a project is not pursuing BREEAM, the same approach supports LEED and WELL lighting credits.
We provide measured photometric data, lighting calculations, a bill of materials and a design that meets the standards above. Contact us for a free, no-obligation quote.