Lighting Levels, Emergency Lighting & Standards

In summary: This page is for building owners, facilities managers, architects and designers who need to know what lighting levels and emergency lighting their project must meet. It summarises the key UK and European standards IJF Lighting designs to, including recommended lux levels, emergency lighting requirements, BREEAM lighting credits and how to avoid obtrusive light. Use it as a guide — every project still needs site-specific lighting calculations.

IJF Lighting designs commercial, residential, architectural and industrial lighting to the relevant UK and European standards. This page summarises the levels and standards we work to. Values are maintained illuminance (Em) and are a guide — every project needs site-specific lighting calculations.

Recommended lighting levels — BS EN 12464-1

SpaceLuxUGRUniformity
General office / open plan500 lux190.6
Meeting rooms500 lux190.6
Reception300 lux220.6
Filing and copying300 lux190.6
Corridors and stairs100 lux280.4
Classrooms (general teaching)300 lux190.6
Whiteboard / teaching wall500 lux vertical190.7
Science labs and practical rooms500 lux190.6
Retail sales floor300 lux220.6
Tills and wrapping500 lux190.6
Warehouse packing and inspection300 lux220.6
Warehouse racking aisles (manned)150 lux220.4
Industrial fine assembly500 lux220.6
Industrial precision work750 lux190.7

BS EN 12464-1 is the principal standard for lighting of indoor workplaces. CIBSE guidance, including the SLL Code for Lighting and LG5 for education, is used alongside it.

Emergency lighting — BS 5266-1:2025, BS EN 1838:2024 and BS EN 50172:2024

  • Escape routes: at least 1 lux at floor level across the full width of the route (less a border). Under BS EN 1838:2024 this is no longer centre-line only.
  • Open areas (anti-panic): at least 0.5 lux at floor level, excluding a 0.5 m perimeter border.
  • High-risk task areas: at least 15 lux, or 10% of the normal task lighting, whichever is greater.
  • Fire-fighting equipment, call points and first-aid points: 5 lux, measured vertically at the point.
  • Duration: 1 hour minimum under BS EN 1838; 3 hours is common practice where premises are not evacuated immediately.
  • Response: 50% of the required illuminance within 5 seconds, 100% within 60 seconds. Uniformity along an escape route no worse than 40:1.
  • Testing: monthly short test and annual full-duration test, following BS EN 50172. Note: BS 5266-1:2025 replaced the 2016 edition in October 2025, and BS EN 1838:2024 replaced the 2013 edition.

Standards we design to

  • BS EN 12464-1:2021 — Lighting of indoor workplaces
  • BS EN 12464-2 — Lighting of outdoor workplaces
  • BS 5266-1:2025 — Emergency lighting, code of practice
  • BS EN 1838:2024 — Emergency lighting
  • BS EN 50172:2024 — Emergency escape lighting systems
  • CIBSE SLL Code for Lighting and relevant CIBSE Lighting Guides
  • Building Regulations Part L (energy) and Part B (fire safety, where it relates to escape lighting)

BREEAM

Hea 01 Visual Comfort (up to 6 credits): glare control to BS EN 12464-1 UGR limits (UGR 19 or lower in offices), daylight provision (typically a daylight factor of 2% or more in occupied spaces), view out, and occupant control of lighting by zone.

Ene 01 Energy Performance: high-efficacy LED luminaires (130 lm/W or better), presence/absence detection, daylight dimming and task-ambient design to reduce installed load — target 8 W/m² or less for office general lighting. Lighting calculations (lux, uniformity and UGR) are required as BREEAM evidence.

Ene 03 External Lighting and Pol 04 Reduction of Night-Time Light Pollution: energy-efficient external fittings and controls to limit spill and upward light.

Neighbours and obtrusive light

Good design should not spill light onto neighbouring properties. We design to the Institution of Lighting Professionals (ILP) Guidance Notes for the Reduction of Obtrusive Light and BS EN 12464-2, limiting sky glow, light trespass into windows, glare to neighbours and upward light, and using curfew dimming and shielded fittings where needed. This also supports BREEAM Pol 04.

Related schemes: where a project is not pursuing BREEAM, the same approach supports LEED and WELL lighting credits.

How IJF Lighting can help

We provide measured photometric data, lighting calculations, a bill of materials and a design that meets the standards above. Contact us for a free, no-obligation quote.